Is your housing company’s electricity connection enough for EV charging? Beta
Enter the main fuse size and the peak power measured by your network operator. The calculator estimates the spare capacity and how many charging points fit without load management and with dynamic load management. Free, no sign-in, and nothing you enter is stored.
Beta version: the calculator’s result is indicative only and does not replace an electrical design or the network company’s connection assessment.
The capacity of a connection follows from its main fuse: P = √3 × 400 V × I, so a 3×63 A connection gives about 43.6 kW. Subtract the peak power measured by the network operator and a 10–20% safety margin, and what remains is the capacity available for charging. Without load management, every charging point is sized for full power. Dynamic load management shares the spare capacity between the cars that are charging, so the same connection usually supports considerably more points.
Result
Enter the measured peak power to see a result. The calculator does not estimate peak power from the number of apartments, because we found no verifiable source for doing so (see below).
- Connection capacity
- –
- Measured peak power
- –
- Safety margin
- –
- Spare capacity for charging
- –
- Without load management
- –
- With dynamic load management
- –
Indicative estimate only. It does not replace an electrical design or the network operator’s review of the connection.
The button opens an email with your inputs and the result already filled in. Nothing is sent until you send the email yourself.
Where do I find the measured peak power?
A Finnish housing company’s connection usually serves several metering points (the apartments and the common property supply), so ask the network operator for the peak power or spare capacity of the whole connection, or check its online service. If the board has no login, ask through the property manager (isännöitsijä).
- Helen Sähköverkko (Helsinki). The Liittymä (connection) page of the Oma Sähköverkko service shows the connection’s spare capacity, and its planning tool shows how many charging points that allows. It requires user rights and at least five metering points on the connection. Helen Sähköverkko: Oma Sähköverkko planning tool (in Finnish) →
- Vantaan Energia Sähköverkot (Vantaa). A free remote assessment for housing companies and businesses in Vantaa: the network operator analyses the connection’s power data and consumption and sends a report. Vantaan Energia Sähköverkot: remote assessment (in Finnish) →
- Caruna. According to Caruna, a housing company’s preliminary study can establish the connection’s spare capacity without a site visit by a professional. Caruna: charging points in housing companies (in Finnish) →
- Elenia. The charging calculator in Elenia Aina is for households with a single metering point on the connection. For housing companies, Elenia advises asking the property manager to check the connection capacity. Elenia: charging calculator (in Finnish) →
- OmaDatahub (Fingrid). Shows a metering point’s consumption at hourly or 15-minute resolution. The data for one metering point, such as the common property supply, may not show the peak of the whole connection if the apartments have their own metering points. Fingrid: OmaDatahub (in Finnish) →
- Other network operators. Ask your network operator’s customer service or online service for the connection’s peak power or spare capacity.
The energy of one hour (kWh) equals that hour’s average power in kilowatts; for 15-minute data, the average power is 4 × kWh. Momentary peaks are higher than these averages, which is why the calculator deducts a safety margin.
How the calculator works
- Connection capacity: P = √3 × 400 V × rated current of the main fuse. The power factor is assumed to be about 1 and the load evenly spread across the phases.
- Safety margin: 10, 15 or 20% of the connection capacity (default 15%). It covers, for example, momentary peaks that hourly or 15-minute averages do not show.
- Spare capacity = connection capacity − measured peak power − safety margin.
- Without load management: points = spare capacity ÷ charging power, rounded down. All points are assumed to charge at full power at the same time, i.e. a diversity factor of 1.0, as in Motiva’s guide.
- With dynamic load management, the spare capacity is shared between the points that are charging. The calculator shows the average power per point when all the points you want charge at once, and how many points can charge at once at the minimum power you choose.
- 3.7 kW = 230 V × 16 A (single-phase), 11 kW ≈ √3 × 400 V × 16 A (three-phase), 1.4 kW ≈ 230 V × 6 A and 4.1 kW ≈ √3 × 400 V × 6 A. The lowest current the charger and the car can regulate to, and how single-phase points are spread across the phases, are checked in the design.
- The calculator does not check the capacity of the main switchboard, rising mains or feeder cables, the protection, or the requirements of SFS 6000-7-722 (the Finnish standard for EV supply installations). Those belong in the electrical design.
Why doesn’t the calculator estimate peak power from the number of apartments?
Peak power can be estimated with methods such as the Velander formula, but it is based on annual energy and area-level coefficients. We found no publicly verifiable source for coefficients that would reliably give a single housing company’s peak from its number of apartments and heating type. The calculator therefore uses the measured peak only. The number of apartments and heating type are passed on to the quote request and shape the notes shown with the result.
Frequently asked questions
How many EV charging points can a housing company’s connection support?
It depends on the connection capacity and the building’s measured peak power. Without load management, the number of points is the spare capacity divided by the charging power: 12 kW of spare capacity is enough for one 11 kW point or three 3.7 kW points. With dynamic load management, more points fit into the same capacity because it is shared between the cars that are charging.
Where does a housing company get the connection’s peak power?
From the network operator. For example, Helen Sähköverkko’s Oma Sähköverkko shows a connection’s spare capacity, and Vantaan Energia Sähköverkot offers housing companies in Vantaa a free remote assessment. With other operators, the figure is available from their online service or customer service, through the property manager if needed.
What does dynamic load management mean?
The charging system measures the building’s total consumption and adjusts the charging points’ power so that the main fuse is never overloaded. Charging uses whatever capacity the building does not need at that moment.
Does the result replace an electrical design?
No. The result is indicative. An electrical design also checks the main switchboard, cabling, protection and the requirements of SFS 6000-7-722, and the network operator carries out its own review of the connection.
Are grants available for charging points?
Applications for Varke’s (formerly ARA) EV charging infrastructure grant have closed. Check Varke and Motiva for any current support. The calculator neither promises nor estimates grants.
Electrical design for housing companies, including EV charging →
What an electrical design includes for a detached house and a housing company: read the guide →
Sources
- SFS 6000-7-722:2022 Low-voltage electrical installations: supply of electric vehicles (SFS)
- SESKO: EV charging recommendation 2025 (in Finnish)
- Motiva: Kiinteistöjen latauspisteet kuntoon (guide, updated 5 Nov 2018; PDF hosted by Elenia, in Finnish)
- Motiva: EV charging and car heating (in Finnish)
- Helen Sähköverkko: connection capacity planning tool in Oma Sähköverkko (9 Oct 2024, in Finnish)
- Vantaan Energia Sähköverkot: remote assessment for EV charging (in Finnish)
- Caruna: charging points in housing companies (in Finnish)
- Elenia: EV charging calculator (18 Oct 2022, in Finnish)
- Fingrid: OmaDatahub customer portal (in Finnish)
- Varke: closed grants, incl. the EV charging infrastructure grant (in Finnish)
Tell us about your project